Select
360 Degree Ceiling Mount PIR Presence Sensor / Fine Motion Sensor -Dual Channel for HVAC and Lighting Control (DALI) - Classrooms, Staff Room and Study Hall
![]() ![]() |



Detection Zone![]() |
Reach: 8 - 20 mts. adjustable in a square detection pattern to eliminate any blind or undetected areas. The fine / small motion area is 8x8 mts. (64 sq.-mts.) |
| Mechanically Adjustable Reach |
The square detection zone can be mechanically adjusted with a potentiometer for specific detection in the area.![]() |
| Technical Highlights | The sensor has 2 channels, one for the DALI dimmable ballast output. The second channel operates the heating, ventilation and air conditioning systems in relation to presence only. |
| Scene Control | The sensor permits two scene control options required for presentations and meetings. With the remote control the user can select dimming levels for each of the channels individually and also select the programmed scenes |
| Applications | Conference rooms, Training Halls and Meeting rooms, Class rooms, Staff room, Office Cabins![]() ![]() |
| Technology | Passive Infrared / PIR - 4800 switching zones and 13 detection levels for sensing small movements normally found in a seated postion, with 4 highly sensitive pyro detectors. The digital technology improves signal evaluation without switching errors. |
Mounting![]() |
Ceiling Mount Passive Infrared PIR Occupancy Sensor - Mounting Height: 2.5 mts to 10 mts. |
| Output |
DALI Output No.1 & No.2 : 12 DALI electronic ballast can be interfaced per output totalling 24 ballast per sensor. HVAC Channel : 1A max. for connection to a relay or contactor to switch HVAC loads. |
| Lighting Channel Output No. 1 Time Setting |
:: 30 sec. - 30 minutes with Pulse mode (approx. 2 sec) :: Automatic time adjustment - The sensor analyzes the movement and automatically adjusts the time delay for the user. :: Basic Brightness Threshold time - 30 sec. - 30 minutes : This time setting can maintain lux level of the lamp when no movement is detected. As soon as a person is present the light intensity is increased to the pre-selected brightness level. |
| HVAC Channel Output No. 2 Time Setting |
:: 1 minutes. - 2 hours - Manually adjustable - switch 'ON' delay :: 0 sec. - 10 minutes, Automatic time adjustment - switch 'OFF' delay. The room surveillance function allows the user to set a delay time before starting the HVAC loads. This feature automatically adjusts the time for the starter based on the movement pattern |
Lux setting facility |
Lux level with Twilight setting can be done through a hand-held remote control. There are 6 typical room situations to choose from. Constant light control with mixed light measurement |
| Master & Slave | Individual luminaires can be hardwired for connecting them in parallel which is suitable for the Master & Slave Operation and enhancement of the zonal coverage of detection.![]() |
Handheld Remote Control![]() |
Infra Red Control available for parameter settings |
Supply![]() |
230V AC 50Hz |
| IP Rating | IP 54 with surface mounting and IP 20 with recessed mounting. |
| Mounting Adapters | ![]() Clamping-type ceiling adapter Control PRO UP BoxSurface-mounting adapter ![]() Control PRO AP Box (IP 54) |